Erico IP6473 Cable to Lug Horizontal Tap Perpendicular t User Manual

Browse online or download User Manual for Accessories for electrical Erico IP6473 Cable to Lug Horizontal Tap Perpendicular t. ERICO IP6473 Cable to Lug Horizontal Tap Perpendicular to Flange User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 1
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Prior to making a connection, read and follow the full instruction sheet IPRF, the full instruction
sheet shipped with CADWELD (IPX) and special instructions below.
Clamp bottom of mold to rail using vise grips.1.
Position lug or cable on mold bottom with gap as shown in sketch.2.
Lock top sections of mold together using E-Z change handles.3.
Position mold top on mold bottom. 4.
Lock top and bottom sections together using frame toggles. 5.
Pack all openings between mold and rail, which may leak molten metal with ERICO packing material. 6.
After completion of weld and waiting periods unlatch toggle clamps and vice grips and remove mold 7.
bottom.
Open E-Z change handle clamp on top section of mold and remove mold. 8.
Note: Use only for connections to contact rail. Do not use for connections to running rail or load bearing rail.
Reference
Mark
Concentric
Cable
Reference
Mark.13" [3.2 mm] Gap
Ropelay Cable
Ropelay Sleeve
Reference
Mark
.25" [6.4 mm] Gap
.25" [6.4 mm] Gap
®
Type "QT" Connection
Type "QV" Connection
Strip Insulation From Cable
Concentric 2" [50.8 mm]
Ropelay Sleeve Length + .13" [3.2 mm]
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT:
www.erico.com
IP6473_B
INSTRUCTION SHEET
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
1 OF 1
© 1995, 2013
ERICO International Corporation
WARNING:
1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
www.erico.com and from your ERICO customer service representative.
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
damage, serious bodily injury and death.
Cable to Lug
Horizontal Tap
Perpendicular
to Flange
Page view 0
1

Summary of Contents

Page 1 - Perpendicular

Prior to making a connection, read and follow the full instruction sheet IPRF, the full instruction sheet shipped with CADWELD (IPX) and special in

Comments to this Manuals

No comments