Installers and Inspectors Guide for CADWELD® Electrical Connections
10www.erico.comProperinspectionofaCADWELD® connection reliesonthejudgmentoftheeldpersonnel.Lookcloselyatthesize,color,surfacenis
11www.erico.comType VSType GTType SSHigher than normalMinimum acceptableNormalHigher than normalMinimum acceptableNormalHigher than normalMinimum acce
12www.erico.comColorThe color of a CADWELD® connection is best seen after a light wire brushing of the connection. It should normally be gold to bronz
13www.erico.comPhotographic GuidesLike all electrical connections, a visual inspection is no guarantee of performance. Crimped or bolted connections c
14www.erico.comGood.A solid weld with only minor surface imperfections.Acceptable.Fillislowerthannormal,butstillsufcient.Acceptable.A worn or
15www.erico.comAcceptable.The presence of water/moisture in conductor strands or mold indicates that one or both were not properly dried. Although the
16www.erico.comReject.Light carbon traces on cable and connection are evidenceofoiloncablestrands.Oilycablesmustbe cleaned with safety solven
17www.erico.comReject.Filltoolow.Weldcavitywasnotlledovercablestrands.“Fins”indicatethatthemoldwasnotclosed tightly due to incorrec
18www.erico.comMostelddifcultiescanbeovercomebycheckingthe following problems.PROBLEM AThe mold doesn’t close tightly.Check for:1. Adjustmen
19www.erico.comPROBLEM DThe connection is porousCheck for:1.Presenceofmoistureeitherinconductorormold.Remedy: (a) Dry the conductor by wiping
2www.erico.comThis handbook is designed to guide the person in the field with the installation and inspection of CADWELD® exothermic welds, including C
20www.erico.com (b) Check to be sure gap is centered under tap hole. NOTE: In some cases, the run (thru) conductor must be cut and gapped. F
21www.erico.comRemedy: (a)SeeProblemF. (b)SeeProblemG. (c)SeeProblemH.4. Conductor movement.PROBLEM JThe riser is too high.Check for:1. Us
22www.erico.comPROBLEM MWhen welding to ductile iron or cast iron, the weld does not “stick” to the surface.Remedy:1. Remove all coatings before clean
23www.erico.comBelowaretypicaleldsituationsrelatedtoCADWELD®ONESHOTconnections.PROBLEM AWeld does not “stick” to ground rod.Remedy:1. Groun
Copperweld is a registered trademark of Copperweld Steel Company, Fayetteville, TN. Cor-Ten is a registered trademark of United States Steel Corp. Eve
3www.erico.comThe CADWELD® Process ... 4The CADWELD Connection ... 5It’s Easy to Make CADWELD Connection
4www.erico.comThe CADWELD® process is a method of making electrical connections of copper to copper or copper to steel in which no outside source of
5www.erico.comThe CADWELD® process is applicable to materials other than copper. Some of these materials are:Common steelChromax*Everdur®Steel railCop
6www.erico.comIt’s Easy to Make CADWELD® ConnectionsDetailed instructions and safety precautions are provided with every CADWELD® mold. You must rea
7www.erico.com3.• Dumptheweldingmaterialintothemold.• Sprinklethestartingmaterialoverthewelding material and onto the lip of the mo
8www.erico.comAll CADWELD® materials are produced to high standards under stringent quality control. All CADWELD connections are designed and tested u
9www.erico.comA CADWELD® mold is designed to last for an average of 50 connections. This will vary according to the care given the mold during use. In