Instruction Manual
LENTON
®
INTERLOK
Rebar Splicing System
Revised January 2013
PDF137_B
Page view 0
1 2 3 4 5 6 ... 27 28

Summary of Contents

Page 1 - Instruction Manual

Instruction ManualLENTON® INTERLOK Rebar Splicing SystemRevised January 2013PDF137_B

Page 2

4www.erico.com1.3 Coupler Dimensions and Determining Cut Length of Reinforcing Steel – Transitions – Imperial Units* “X” Min. Type 1 and “Y” Min. Typ

Page 3 - Table of Contents

5www.erico.com1.3 Coupler Dimensions and Determining Cut Length of Reinforcing Steel – Transitions – Metric Units* “X” Min. Type 1 and “Y” Min. Type

Page 4

6www.erico.com1.4 How to Determine Inlet and Outlet Straight Tube LengthsTo Determine Inlet and Outlet Tube Length:Distance from edge of panel to cen

Page 5 - Foreword

7www.erico.com1.5 Locating Inlet/Outlet Tubes for Pump Filling ApplicationWhen the Placing Drawings specify a Pump Fill Application, inlet and outlet

Page 6 - Overview

8www.erico.com1.5 Locating Inlet/Outlet Tubes for Pump Filling ApplicationForming:Occasionally it is necessary to bend the PVC tube to route it around

Page 7 - Precaster Installation

9www.erico.com1.6 Coupler Installation Procedures at Precasting PlantA. Attaching Coupler To Rebar: 1. Remove the thread protector. Examine threaded

Page 8

10www.erico.com1.6Coupler Installation Procedures at Precasting PlantC. Install Inlet and Outlet Tubes:Refer to the Placing Drawings to determine if

Page 9

11www.erico.comJob Site Grouting2.1 Quantity of LENTON® INTERLOK Splices per Bag of HY10LHY10L is provided in 50 pound (22.7 Kg) bagsThe values given

Page 10 - Imperial Units:

12www.erico.com2.2 HY10L Mixing Instructions1 Preparation:1.1 Materials and Equipment Needed for Proper Use and Installation:To permit rapid and conti

Page 11 - Metric Units:

13www.erico.com2.2 HY10L Mixing InstructionsIt is recommended that the fluidity be measured on every batch (bag) mixed until the user becomes familiar

Page 13

14www.erico.com2.3 Hot and Cold Weather Grouting InstructionsThe HY10L filler material is designed to be used with the LENTON® INTERLOK rebar splicing

Page 14

15www.erico.com2.3 Hot and Cold Weather Grouting Instructions 5. The HY10L grout at time of placement should be a minimum of 50°F (10°C) and no high

Page 15

Dowel LengthSealing MortarEmbedment LengthInlet andOutlet PlugsSealing MortarMeasure “A”16www.erico.com2.4 Gravity Fill Installation Instructions For

Page 16

17www.erico.com2.4 Gravity Fill Installation Instructions For HY10L Filler Material6) Mix the HY10L according to the mixing directions on the bag. U

Page 17 - 2.1 Quantity of LENTON

18www.erico.com2.5 Pump Fill Installation Instructions For HY10L Filler Material(Vertical, Horizontal and Inclined Application as Shown in Figure 1)Th

Page 18 - 2.2 HY10L Mixing Instructions

19www.erico.com2.5 Pump Fill Installation Instructions For HY10L Filler Material12) Once the HY10L has set (usually the next day), the plugs can be r

Page 19

20www.erico.com2.6 Grouting Troubleshooting GuideI. Recommended Equipment:1. A large piston or garden sprayer filled with water (4 gallon or larger)

Page 20

21www.erico.com2.7 HY10L Filler Material Product SpecificationHY10L filler material is a specially formulated ready to use grout designed for use in t

Page 21

PDF137_B C1430IS12WWEN 0.1M0613ACI is a registered trademark of American Concrete Institute.ASTM is a registered trademark of American Soci

Page 22 - For HY10L Filler Material

iwww.erico.comTable of ContentsGeneral and Safety Information iiForeword iiiOverview iv1. Precaster Installation PAGE 1.1 Components Lis

Page 23

IMPORTANT – General and Safety InformationA. Only ERICO authorized materials should be used to make LENTON® INTERLOK Rebar Splices. 1. Do not sp

Page 24

iiiwww.erico.comForewordThe LENTON® INTERLOK System has been designed to exceed the ACI® 318 Building Code Type 1 requirement of developing, in both t

Page 25

ivwww.erico.comOverviewThe LENTON® INTERLOK Mechanical Reinforcing Steel Splice is designed to connect #5 (16 mm) through #18 (57 mm) rebar, conformin

Page 26 - SOLUTION

1www.erico.comPrecaster InstallationI.I Component List:Item No. Description Standard Item Included Separate Order1 LENTON® INTERLOK Coupler Standard2

Page 27

2www.erico.comTo Determine Typical Cut Length of Reinforcing Steel:Maximum Cut Length Gravity or Pump Condition = [Overall Panel Height - E] + Sealin

Page 28

3www.erico.com1.2 Coupler Dimensions and Determining Cut Length of Reinforcing Steel – Metric Units* “X” Min. Type 1 will develop 125% of the specifi